High Hazard Group H

High Hazard Group H


Group H-5 occupancies only and occupancies used for the manufacture of organic coatings
Manual fire alarm system: pull stations at all exits, every level staircase and elevator lobby; common areas notification appliances activated by any pull station.
Group H occupancies involved with highly toxic gases, organic peroxides and oxidizers
Automatic fire alarm system: common areas notification appliances and smoke detection system. Common areas notification appliances activated by any smoke detector.
907.2.5 Group H. A manual fire alarm system that
activates the occupant notification system in accordance
with Section 907.5 shall be installed in Group H-5 occupancies
and in occupancies used for the manufacture of
organic coatings. An automatic smoke detection system
shall be installed for highly toxic gases, organic peroxides
and oxidizers in accordance with Chapters 60, 62 and 63,
respectively, of the California Fire Code.
2016 CBC 907.2.5

Group H occupancies located above 10th story
Manual fire alarm boxes shall be required on each side of the 2-hour fire-smoke barrier and at each exit.
907.2.5.1 Group H occupancies located above the
10th story. Manual fire alarm boxes shall be required
on each side of the 2-hour fire-smoke barrier and at
each exit above the 10th story.

2016 CBC 907.2.5.1
2016 CBC 907.2.5.1


Additional Requirements as applicable.
 