Organized Camps Group C

Organized Camps Group C


Occupancy is sprinklered
Automatic fire alarm system: common use areas notification appliances and smoke detection system. Smoke detectors shall be installed in all common use areas. Sprinkler riser monitoring shall be provided. Common areas notification appliances activated by any smoke detector or by sprinkler waterflow switch.
Occupancy is NOT sprinklered
Automatic fire alarm system: common use areas notification appliances and smoke detection system. Smoke detectors shall be installed in all common use areas. Common areas notification appliances activated by any smoke detector.
907.2.25.1 General. Every building and structure used
or intended for sleeping purposes shall be provided
with an automatic smoke-detection system.

Exceptions:
1. Buildings and structures in existence and in operation
prior to January 1, 1985.
2. Tents, tent structures and buildings and structures
that do not exceed 25 ft (7620 mm) in any lateral
dimensions and where such building or structure
is not more than one story.


2016 CBC 907.2.25.1

Additional requirements as applicable
 
www.rpefire.com