Organized Camps Group C

Organized Camps Group C


Occupancy is sprinklered
Automatic fire alarm system: common use areas notification appliances and smoke detection system. Smoke detectors shall be installed in all common use areas. Sprinkler riser monitoring shall be provided. Common areas notification appliances activated by any smoke detector or by sprinkler waterflow switch.
Occupancy is NOT sprinklered
Automatic fire alarm system: common use areas notification appliances and smoke detection system. Smoke detectors shall be installed in all common use areas. Common areas notification appliances activated by any smoke detector.
907.2.25.1 General. Every building and structure
used or intended for sleeping purposes shall be provided
with an automatic smoke-detection system.

Exceptions:
1. Buildings and structures in existence and in operation
prior to January 1, 1985.

2. Tents, tent structures and buildings and structures
that do not exceed 25 ft (7620 mm) in any lateral
dimensions and where such building or structure
is not more than one story.

2019 CBC 907.2.25.1

Camp audible alarms
Exterior audible alarms shall be provided throughout camp grounds.
907.2.25.2 Camp fire alarm. Every organized camp
shall provide and maintain audible appliances, or
devices suitable for sounding afire alarm. Such audi-
ble appliances or devices may be of any type accept-
able to the enforcing agency provided they are
distinctive in tone from all other signaling devices or
systems and shall be audible throughout the camp
premises. When an automatic fire alarm system is pro-
vided, as required by Section 450.6.6 of the California
Building Code, all audible appliances required by this
section shall be of the same type as that used in the
automatic system.

2019 CBC 907.2.25.2
2019 CBC 907.2.25.2


Additional Requirements as applicable.
 